CB-7080 & CB-7080D Counter/Timer Document Revision 2 August 2005 © Copyright 2015 User's Guide Guide
CB-7080 & CB-7080D Counter/Timer User's Guide Default settings 1-6 Counter input measurement Perform the following procedure to measure the
CB-7080 & CB-7080D Counter/Timer User's Guide Application notes 1-7 Counter alarm mode selection There are no alarm functions in frequency m
CB-7080 & CB-7080D Counter/Timer User's Guide Application notes 1-8 Table 1-4 Digital Alarm Configuration D/O 0 D/O 1 Frequency mode D/O 0
CB-7080 & CB-7080D Counter/Timer User's Guide Application notes 1-9 Gate control setting The gate control is ignored in frequency mode (51).
CB-7080 & CB-7080D Counter/Timer User's Guide Application notes 1-10 Counter input applications The counter mode type is indicated by enteri
2-1 2 Command Set Overview The commands in this section are grouped by function, and summarized as listed below. Table Function Description Table
CB-7080 & CB-7080D Counter/Timer User's Guide General syntax format 2-2 Delimiter characters The characters %, #, ~, %, $, @ are used as the
CB-7080 & CB-7080D Counter/Timer User's Guide General syntax format 2-3 Command Response Description Reference $AA1L !AA(data) Read the low
CB-7080 & CB-7080D Counter/Timer User's Guide %AANNTTCCFF 2-4 %AANNTTCCFF Description: Set the configuration of a module. Syntax: %AANNTTCCF
CB-7080 & CB-7080D Counter/Timer User's Guide #AAN 2-1 #AAN Description: Read the counter or frequency value. Syntax: #AAN[chk](cr) # A del
HM CB-7080.doc Your new Measurement Computing product comes with a fantastic extra — Management committed to your satisfaction! Thank you for cho
CB-7080 & CB-7080D Counter/Timer User's Guide ~** 2-2 ~** Description: The host sends this command to tell all modules “Host is OK”. Syntax:
CB-7080 & CB-7080D Counter/Timer User's Guide ~AA0 2-3 ~AA0 Description: Reads the module status. The module status will be latched until ~A
CB-7080 & CB-7080D Counter/Timer User's Guide ~AA1 2-4 ~AA1 Description: Resets the module status. The module status will be latched until ~
CB-7080 & CB-7080D Counter/Timer User's Guide ~AA2 2-5 ~AA2 Description: Reads the status and timer value of host watchdog. When the host wa
CB-7080 & CB-7080D Counter/Timer User's Guide ~AA3ETT 2-6 ~AA3ETT Description: Enable/disable the timer value of host watchdog. The host wat
CB-7080 & CB-7080D Counter/Timer User's Guide ~AAAS 2-7 ~AAAS Description: Sets counter alarm mode. Refer to "Counter alarm mode select
CB-7080 & CB-7080D Counter/Timer User's Guide ~AAO(name) 2-8 ~AAO(name) Description: Sets the module name. Syntax: ~AAO(name)[chk](cr) ~ A
CB-7080 & CB-7080D Counter/Timer User's Guide $AA0H 2-9 $AA0H Description: Reads the minimum input signal width at high level. Refer to &q
CB-7080 & CB-7080D Counter/Timer User's Guide $AA0H(data) 2-10 $AA0H(data) Description: Sets the minimum input signal width at high level. R
CB-7080 & CB-7080D Counter/Timer User's Guide $AA0L 2-11 $AA0L Description: Read the minimum input signal width at low level. Refer to "
iii Table of Contents 1 Introduction ... 1-1 Comparing the 708
CB-7080 & CB-7080D Counter/Timer User's Guide $AA0L(data) 2-12 $AA0L(data) Description: Sets the minimum input signal width at low level. Re
CB-7080 & CB-7080D Counter/Timer User's Guide $AA1H 2-13 $AA1H Description: Reads the high trigger level of non-isolated input. Refer to &qu
CB-7080 & CB-7080D Counter/Timer User's Guide $AA1H(data) 2-14 $AA1H(data) Description: Sets the high trigger level of non-isolated inputs.
CB-7080 & CB-7080D Counter/Timer User's Guide $AA1L 2-15 $AA1L Description: Read the Low trigger level of non-isolated input. Refer to "
CB-7080 & CB-7080D Counter/Timer User's Guide $AA1L(data) 2-16 $AA1L(data) Description: Set the low trigger level of non-isolated input. Ref
CB-7080 & CB-7080D Counter/Timer User's Guide $AA2 2-17 $AA2 Description: Read the configuration of module. Syntax: $AA2[chk](cr) $ A delim
CB-7080 & CB-7080D Counter/Timer User's Guide $AA3N 2-18 $AA3N Description: Read the maximum counter value. Syntax: $AA3N[chk](cr) $ A deli
CB-7080 & CB-7080D Counter/Timer User's Guide $AA3N(data) 2-19 $AA3N(data) Description: Set the maximum counter value. Syntax: $AA3N(data)[c
CB-7080 & CB-7080D Counter/Timer User's Guide $AA4 2-20 $AA4 Description: Read the status of digital filter. Refer to "Digital filter s
CB-7080 & CB-7080D Counter/Timer User's Guide $AA4S 2-21 $AA4S Description: Set the filter status. Refer to "Digital filter setting&quo
CB-7080 & CB-7080D Counter/Timer User's Guide iv $AA7N ...
CB-7080 & CB-7080D Counter/Timer User's Guide $AA5N 2-22 $AA5N Description: Read the counter status Syntax: $AA5N[chk](cr) $ A delimiter ch
CB-7080 & CB-7080D Counter/Timer User's Guide $AA5NS 2-23 $AA5NS Description: Set the counter status Syntax: $AA5NS[chk](cr) $ A delimiter
CB-7080 & CB-7080D Counter/Timer User's Guide $AA6N 2-24 $AA6N Description: Reset counter 0 or counter 1 to the preset value and clear the o
CB-7080 & CB-7080D Counter/Timer User's Guide $AA7N 2-25 $AA7N Description: Read the overflow flag of counter. You can use the $AA6S command
CB-7080 & CB-7080D Counter/Timer User's Guide $AA8 2-26 $AA8 Description: Read the LED configuration. Syntax: $AA8[chk](cr) $ A delimiter c
CB-7080 & CB-7080D Counter/Timer User's Guide $AA8V 2-27 $AA8V Description: Select LED Configuration. Syntax: AA8V[chk](cr) $ A delimiter c
CB-7080 & CB-7080D Counter/Timer User's Guide $AA9(data) 2-28 $AA9(data) Description: Send data to the LED display. Syntax: $AA9(data)[chk](
CB-7080 & CB-7080D Counter/Timer User's Guide $AAG 2-29 $AAG Description: Read gate control mode. Refer to "Gate control setting"
CB-7080 & CB-7080D Counter/Timer User's Guide $AAAG 2-30 $AAAG Description: Set gate control mode. Refer to "Gate control setting"
CB-7080 & CB-7080D Counter/Timer User's Guide $AAB 2-31 $AAB Description: Read input mode. Refer to "Counter/Frequency input mode selec
1-1 1 Introduction CB-7000 is a family of network data acquisition and control modules. They provide A/D, D/A, DI/O, Timing/Counting and other functi
CB-7080 & CB-7080D Counter/Timer User's Guide $AABS 2-32 $AABS Description: Set input mode. Refer to "Counter/Frequency input mode sele
CB-7080 & CB-7080D Counter/Timer User's Guide $AAF 2-33 $AAF Description: Read the version number of firmware. Syntax: $AAF[chk](cr) $ A d
CB-7080 & CB-7080D Counter/Timer User's Guide $AAI 2-34 $AAI Description: Read the value of *INIT pin. Syntax: $AAI[chk](cr) $ A delimiter
CB-7080 & CB-7080D Counter/Timer User's Guide $AAM 2-35 $AAM Description: Read the module name. Syntax: $AAM[chk](cr) $ A delimiter charact
CB-7080 & CB-7080D Counter/Timer User's Guide @AADI 2-36 @AADI Description: Read the status of the D/O and the alarm. Refer to "Counter
CB-7080 & CB-7080D Counter/Timer User's Guide @AADI 2-37 Examples: Alarm disabled. D/O0=D/O1=OFF: command: @01DI(cr) response: !0100000(cr
CB-7080 & CB-7080D Counter/Timer User's Guide @AADO0D 2-38 @AADO0D Description: Set digital output. Syntax: @AADO0D[chk](cr) @ A delimiter
CB-7080 & CB-7080D Counter/Timer User's Guide @AAEAN 2-39 @AAEAN Description: Enable the counter alarm (for alarm-mode 0). Refer to "Co
CB-7080 & CB-7080D Counter/Timer User's Guide @AAEAT 2-40 @AAEAT Description: Enable the counter alarm (for alarm-mode 1). Refer to "Co
CB-7080 & CB-7080D Counter/Timer User's Guide @AACA 2-41 @AACA Description: Clear latch alarm (for alarm-mode 1). Refer to "Counter ala
CB-7080 & CB-7080D Counter/Timer User's Guide Pin assignments 1-2 Pin assignments The pin names and locations on the CB-7080D module are sho
CB-7080 & CB-7080D Counter/Timer User's Guide @AADA 2-42 @AADA Description: Disable alarm (for alarm-mode 1). Refer to "Counter alarm m
CB-7080 & CB-7080D Counter/Timer User's Guide @AADAN 2-43 @AADAN Description: Disable alarm (for alarm-mode 0). Refer to "Counter alarm
CB-7080 & CB-7080D Counter/Timer User's Guide @AAGN 2-44 @AAGN Description: Read the preset value of counter. The $AA6 command can reset cou
CB-7080 & CB-7080D Counter/Timer User's Guide @AAPN(data) 2-45 @AAPN(data) Description: Set the preset value of counter. The $AA6 command ca
CB-7080 & CB-7080D Counter/Timer User's Guide @AAPA(data) 2-46 @AAPA(data) Description: Set the alarm limit of counter 0 (for alarm mode 0).
CB-7080 & CB-7080D Counter/Timer User's Guide @AAPA(data) 2-47 @AAPA(data) Description: Set the Hi-alarm limit of counter 0 (for alarm mode
CB-7080 & CB-7080D Counter/Timer User's Guide @AASA(data) 2-48 @AASA(data) Description: Set alarm limit of counter-1(for alarm-mode 0). Refe
CB-7080 & CB-7080D Counter/Timer User's Guide @AASA(data) 2-49 @AASA(data) Description: Set the Hi-Hi alarm limit of counter 0 (for alarm-mo
CB-7080 & CB-7080D Counter/Timer User's Guide @AARP 2-50 @AARP Description: Read the alarm limit of counter 0 (for alarm-mode 0). Refer to &
CB-7080 & CB-7080D Counter/Timer User's Guide @AARP 2-51 @AARP Description: Read the Hi-alarm limit of counter 0 (for alarm-mode 1). Refer t
CB-7080 & CB-7080D Counter/Timer User's Guide Functional block diagram 1-3 Digital output Capacity 2 channels, open-collector to 30 V, 30 mA
CB-7080 & CB-7080D Counter/Timer User's Guide @AARA 2-52 @AARA Description: Read the alarm limit of counter-1 (for alarm-mode 0). Refer to &
CB-7080 & CB-7080D Counter/Timer User's Guide @AARA 2-53 @AARA Description: Read the Hi-Hi-alarm limit of counter 0 (for alarm-mode 1). Refe
3-1 3 Operating principle and application notes INIT*_pin operation principle All CB-7000 modules contain an EEPROM to store configuration informatio
EC Declaration of Conformity We, Measurement Computing Corporation, declare under sole responsibility that the product: CB-7080 2 channel 32-bit
Measurement Computing Corporation 10 Commerce Way Suite 1008 Norton, Massachusetts 02766 (508) 946-5100 Fax: (508) 946-9500 E-mail: [email protected]
CB-7080 & CB-7080D Counter/Timer User's Guide Application wiring 1-4 Application wiring Output drive to SSR or other load CB-7080 and CB-70
CB-7080 & CB-7080D Counter/Timer User's Guide Application wiring 1-5 Counter input Ext. GNDExt. 24VRS-485 Data-RS-485 Data-76543821910GND+V